SkyAir Heat Pump (Cold Climate) Horizontal 10" High Static

1.5-4 Tons  |  Model: RZA + FBA_A

Refrigerant: R-32

Model: RZA

Heat Pump (Cold Climate)
Max VerticalLength (ft)98' (18-48 MBH)Max Total Length (ft)230' (18-48 MBH)

Model: FBA_A

Horizontal 12" High Static

Dimensions (H x W x D)

18-48 MBH: 34-1/4'' x 43-5/16'' x 18-1/8''

Dimensions (H x W x D)

18-24 MBH: 9–11/16'' × 39–3/8'' × 31–1/2''
30-48 MBH: 9–11/16'' × 55–1/8'' × 31–1/2''

Heating Capacities (BTU/HR)Piping
Model NumberNominal Size (MBH)Indoor Unit CFM (High/Medium/Low)Nominal Cooling @95°F (BTU/HR)43°FWB 5°FWB-4°FWBLineset SizeMax Total Length (ft)Max Vertical Length (ft)Energy Star Certified
FBA18AAVJU + RZA18AAVJU18635/565/51218,00020,00020,20017,3003/8'' x 5/8''23098No
FBA24AAVJU + RZA24AAVJU24742/635/56524,00027,00021,00017,9003/8'' x 5/8''23098No
FBA30AAVJU + RZA30AAVJU301,094/936/79530,00034,00037,00030,3003/8'' x 5/8''23098No
FBA36AAVJU + RZA36AAVJU361,130/953/79536,00040,00037,60030,1003/8'' x 5/8''23098No
FBA42AAVJU + RZA42AAVJU421,377/1,130/91840,50047,00038,50030,1003/8'' x 5/8''23098No
FBA48AAVJU + RZA48AAVJU481,377/1,130/91848,00054,00038,50030,1003/8'' x 5/8''23098No

  • Nominal Cooling Capacities @ 95°F DB OAT;
  • Heating operation range -4°F to 60°F (Extended heating down to -13°F)
  • Cooling operation range 23°F to 122°F
  • Estimated heating capacities at lower ambient temperatures do not include derates for defrost operation.
  • Condensing units to be elevated above local snow levels (normally 18" above mounting surface in cold climates).
  • Requires field supplied filter racks and filters. Work with local Daikin manufacturers representatives for options.

Outdoor Unit Features

  • SkyAir cold climate model with up to 100% heating capability down to 0°F.
  • Long pipe lengths with 98' vertical separation and 230' total length.
  • Low outdoor unit sound between 56-59 dB(A).
  • Year round comfort and energy savings with Variable Refrigerant Temperature technology (VRT).
  • New single chassis size across all RZA models.

Indoor Unit Features

  • Factory-installed coil refrigerant leak detection sensor.
  • Dispersion mode with higher airflow rate for refrigerant dispersion in the event of a leak.
  • Medium profile height of 9-11/16" for all models
  • Designed for quiet operation, with sound levels as low as 32 dB(A).
  • Powerful static pressure capability, with up to 0.8" w.g. ESP.
  • Ease of installation with auto adjusting airflow at commissioning based on ESP.
  • Integral condensate pump with up to 18-3/8" of lift from the drain outlet.
  • 10 year parts warranty.

Electrical Information

MCA (A) / MOP (A)
TypeVoltage18 MBH24 MBH30 MBH36 MBH42 MBH48 MBH
Indoor unit208-230V/1ph1.9 / 151.9 / 153.0 / 153.1 / 153.6 / 153.6 / 15
Outdoor unit208-230V/1ph19.8 / 2019.8 / 2034.6 / 3534.6 / 3534.6 / 3534.6 / 35