SkyAir Heat Pump (Cold Climate) 33" x 33" Cassettes

1.5-4 Tons  |  Model: RZQ + FCQ_A

Refrigerant: R-410A

***Warning: Transitioned to R-32***

Model: RZQ

Heat Pump (Cold Climate)
Max VerticalLength (ft)98' (18-48 MBH)Max Total Length (ft)164' (18-24 MBH)230' (30-48 MBH)

Model: FCQ_A

33" X 33" Ceiling Cassette

Dimensions (H x W x D)

18-24 MBH: 39'' × 37'' × 12–5/8''
30-48 MBH: 52–15/16'' × 35–7/16'' × 12–5/8''

Dimensions (H x W x D)

18-24 MBH: 9–11/16'' × 33–1/16'' × 33–1/16''
30-48 MBH: 11–11/32'' × 33–1/16'' × 33–1/16''

Heating Capacities (BTU/HR)Piping
Model NumberNominal Size (MBH)Indoor Unit CFM (High/Medium/Low)Nominal Cooling @95°F (BTU/HR)43°FWB 5°FWB-4°FWBLineset SizeMax Total Length (ft)Max Vertical Length (ft)
FCQ18AAVJU + RZQ18TBVJUA18742/618/47718,00020,00020,00017,0003/8'' x 5/8''16498
FCQ24AAVJU + RZQ24TBVJUA24777/618/47724,00027,00021,40017,6003/8'' x 5/8''16498
FCQ30AAVJU + RZQ30TBVJUA301,112/918/67130,00034,00034,00033,0003/8'' x 5/8''23098
FCQ36AAVJU + RZQ36TBVJUA361,165/918/67136,00040,00040,00035,0003/8'' x 5/8''23098
FCQ42AAVJU + RZQ42TBVJUA421,218/971/74242,00047,00041,00036,0003/8'' x 5/8''23098
FCQ48AAVJU + RZQ48TBVJUA481,218/971/74248,00054,00041,00036,0003/8'' x 5/8''23098

  • Nominal Cooling Capacities @ 95°F DB OAT;
  • Heating operation range -4°F to 60°F (Extended heating down to -13°F)
  • Cooling operation range 23°F to 122°F
  • Estimated heating capacities at lower ambient temperatures do not include derates for defrost operation.
  • Condensing units to be elevated above local snow levels (normally 18" above mounting surface in cold climates).
  • Requires separate decoration panel (available with self cleaning filter option).

Outdoor Unit Features

  • SkyAir cold climate model with up to 100% heating capability down to 0°F.
  • Long pipe lengths with 98' vertical separation and 164' to 230' total length.
  • Low outdoor unit sound between 57-61 dB(A).
  • Year round comfort and energy savings with Variable Refrigerant Temperature technology (VRT).

Indoor Unit Features

  • True 360° Airflow and three room sensors enables optimized occupant comfort and efficiency.
  • Sound pressure levels as low as 27 db(A).
  • Factory installed washable filters as standard with options for MERV 13 filters.
  • OA integration options for up to 20% OA using a fresh air intake kit that adds 2.36'' of height to the unit.
  • Independently configurable auxiliary heat integration settings.
  • Roundflow, 4-way, and 3-way blow configurability.
  • MERV 13 air filter kit available (not compatible with self cleaning filter decoration panel).
  • Individual air louver control.
  • Integral condensate pump with up to 26-1/2'' lift.
  • 10 year parts warranty.

Electrical Information

MCA (A) / MOP (A)
TypeVoltage18 MBH24 MBH30 MBH36 MBH42 MBH48 MBH
Indoor unit208-230V/1ph0.5 / 150.5 / 151.0 / 151.6 / 151.6 / 151.6 / 15
Outdoor unit208-230V / 1ph16.5 / 2016.5 / 2029.1 / 3529.1 / 3529.1 / 3529.1 / 35

Submittal Data Sheets