VRV Emerion Heat Pump
Standard Heating (-22°F) High Ambient Cooling (122°F)
| Model Number | Nominal Size | Nominal Cooling (BTU/hr) | Nominal Heating (BTU/hr) | Estimated Heating 0°F & -13°F (BTU/hr) | Cooling Efficiency (non-ducted) (IEER) | Heating Efficiency (non-ducted) 47°F & 17°F (COP) | Airflow (CFM) | Net Weight (lb) |
|---|---|---|---|---|---|---|---|---|
| RXYA72A | 6 Tons | 72,000 | 81,000 | 59,100 / 46,100 | 27 | 4.00 / 2.49 | 6,200 | 549 |
| RXYA96A | 8 tons | 96,000 | 108,000 | 79,200 / 69,200 | 28.5 | 4.10 / 2.53 | 8,965 | 736 |
| RXYA120A | 10 Tons | 119,000 | 135,000 | 84,800 / 74,400 | 26.6 | 3.77 / 2.46 | 8,965 | 739 |
| RXYA144A | 12 Tons | 144,000 | 162,000 | 109,000 / 95,100 | 25.4 | 3.70 / 2.18 | 9,675 | 825 |
| RXYA168A | 14 Tons | 162,000 | 189,000 | 109,000 / 93,900 | 23.4 | 3.40 / 2.18 | 9,675 | 827 |
| RXYA192A | 16 Tons | 192,000 | 216,000 | 136,000 / 119,000 | 23.6 | 3.66 / 2.22 | 13,650 | 1010 |
| RXYA216A | 18 Tons | 216,000 | 243,000 | 140,000 / 123,000 | 22.2 | 3.62 / 2.18 | 14,505 | 1010 |
| RXYA240A | 20 Tons | 238,000 | 270,000 | 142,000 / 124,000 | 21.8 | 3.42 / 2.16 | 14,505 | 1010 |
Notes
Features
- New improved D4 net provides faster communication speeds and larger data volume compared to the D3 net up to 30 times the amount of data compared to D3 net
- Reduced install and commissioning time through auto addressing feature with D4 communications protocol
- Increased energy savings through new improved VRT technology with evaporation temperature control at each indoor unit (SSOV required)
- New remote field setting option that allows data retrieval and field setting changes of units on the system from anywhere, without the need for physical access to each room
- Vertical separation up to 361 FT with field setting
- New field setting that allows reuse of R410Aa piping network for new R32 system, eliminating need to replace for retrofit applications
- Hot gas defrost circuit allows for installation without base pan heater
- Design flexibility to enlarge system from single to a dual-module without changes to installed main pipe sizes for phased installation or tenant fit-out buildings
- High dust moisture protection with an IP55 rated sealed E-box
- Built-in data recorder to store up to 45 minutes of operational data
- Integrates with new Daikin HERO ecosystem, an IoT -based remote monitoring and diagnostics platform
- Extend benefits of inverter technology to custom terminal units and AHUs through AHU integration kits
Electrical Information
| MCA (A) / MOP (A) | |||||||||
|---|---|---|---|---|---|---|---|---|---|
| Availability | Voltage | 6 Tons | 8 tons | 10 Tons | 12 Tons | 14 Tons | 16 Tons | 18 Tons | 20 Tons |
| 208-230 / 60 / 3 | 33 / 35 | 34.9 / 40 | 40 / 45 | 50 / 60 | 60.2 / 70 | 64.2 / 80 | 70 / 80 | 79.1 / 90 | |
| 460 / 60 / 3 | 14.9 / 20 | 17.5 / 20 | 18.2 / 25 | 23.3 / 30 | 27.1 / 30 | 30.7 / 35 | 32.8 / 40 | 35.1 / 40 | |
Submittal Data Sheets
| 208-230 / 60 / 3 | 460 / 60 / 3 | |
|---|---|---|
| 6 Tons | RXYA72AATJA | RXYA72AAYDA |
| 8 tons | RXYA96AATJA | RXYA96AAYDA |
| 10 Tons | RXYA120AATJA | RXYA120AAYDA |
| 12 Tons | RXYA144AATJA | RXYA144AAYDA |
| 14 Tons | RXYA168AATJA | RXYA168AAYDA |
| 16 Tons | RXYA192AATJA | RXYA192AAYDA |
| 18 Tons | RXYA216AATJA | RXYA216AAYDA |
| 20 Tons | RXYA240AATJA | RXYA240AAYDA |
| 22 Tons | RXYA264AATJA | RXYA264AAYDA |
| 24 Tons | RXYA288AATJA | RXYA288AAYDA |
| 26 Tons | RXYA312AATJA | RXYA312AAYDA |
| 28 Tons | RXYA336AATJA | RXYA336AAYDA |
| 30 Tons | RXYA360AATJA | RXYA360AAYDA |
| 32 Tons | RXYA384AATJA | RXYA384AAYDA |
| 34 Tons | RXYA408AATJA | RXYA408AAYDA |
| 36 Tons | RXYA432AATJA | RXYA432AAYDA |
| 38 Tons | RXYA456AATJA | RXYA456AAYDA |
| 40 Tons | RXYA480AATJA | RXYA480AAYDA |