Vertical High Static ECM (0.9")

9.5 to 60 MBH  |  Model: FXTQ_T

Refrigerant: R-410A

***Warning: Transitioning to R-32***
Model NumberNominal Size (MBH)CFM (High/Low)Nominal Cooling (BTU/hr)Nominal Heating (BTU/hr)Dimensions (HxWxD)VoltageMCA (A)MOP (A)
FXTQ09TAVJUD9.5300 / 275 / 2509,50010,500208/230V - 1ph4.915
FXTQ12TAVJUD12400 / 340 / 28012,00013,500208/230V - 1ph4.915
FXTQ18TAVJUD18600 / 510 / 42018,00020,000208/230V - 1ph4.915
FXTQ24TAVJUD24800 / 680 / 56024,00027,000208/230V - 1ph4.915
FXTQ30TAVJUD301000 / 850 / 70030,00034,000208/230V - 1ph4.915
FXTQ36TAVJUD361050 / 900 / 75036,00040,000208/230V - 1ph4.915
FXTQ42TAVJUD421400 / 1190 / 98042,00046,000208/230V - 1ph6.515
FXTQ48TAVJUD481520 / 1290 / 106048,00054,000208/230V - 1ph6.515
FXTQ54TAVJUD541800 / 1530 / 126054,00060,000208/230V - 1ph8.615
FXTQ60TAVJUD601800 / 1530 / 126160,00066,000208/230V - 1ph8.615
Notes
  • Nominal Cooling Capacities @ 80/67 °F DB/WB EAT: Nominal Heating Capacities @ 70°F DB EAT. Recommended cooling operation range 57-77°F WB EAT and 80% RH or lower. Recommended heating operation range 59-80°F DB EAT and 80% RH or lower. Always use Daikin WebXpress software to understand true capacities at design conditions.

Features

  • Full multi-position air handler capable of upflow, downflow, horizontal right, and horizontal left installation. Designed for quiet operation, with sound levels as low as 36 dB(A). High efficiency EC motors to deliver nominal CFM at up to 0.9” w.g. static. Designed with less than 2% air leakage when tested in accordance with ASHRAE standard 193. Optional electric heat accessories from 3kW to 25kW with single point power. Easily integrate with third party accessories such as a humidifier or economizer with on-board contacts. Options for gravity drained condensate or field installed pump. 10 year parts warranty.

Submittal Data Sheets

208/230V - 1ph
9.5FXTQ09TAVJUD
12FXTQ12TAVJUD
18FXTQ18TAVJUD
24FXTQ24TAVJUD
30FXTQ30TAVJUD
36FXTQ36TAVJUD
42FXTQ42TAVJUD
48FXTQ48TAVJUD
54FXTQ54TAVJUD
60FXTQ60TAVJUD