Cold Climate (Aurora Series) Heat Pump (-13F) Wall Mounted

0.75 to 2 Tons  |  Model: RXL + FTX_W

Refrigerant: R-410A

***Warning: Transitioned to R-32*** - See replacement RXM + FTXM_W

Model: RXL

Wall Mounted
(Cold Climate Heating to -13F)
Max VerticalLength (ft)49' (9-12 MBH)66' (15-24 MBH)Max Total Length (ft)66' (9-12 MBH)98' (15-24 MBH)

Model: FTX_W

Dimensions (H x W x D)

9-12 MBH: 21-5/8" × 26-9/16" × 11-3/16"
15-24 MBH: 28-15/16" × 34-1/4" × 12-5/8"

Dimensions (H x W x D)

9-12 MBH: 11-1/4" × 30-5/16" × 8-3/4"
15-15 MBH: 11-5/8" × 39" × 10-3/8"
18-24 MBH: 13-3/8" × 41-5/16" × 10-1/4"

Heating Capacities (BTU/HR)Piping
Model NumberNominal Size (MBH)Indoor Unit CFM (High/Medium/Low/Super Low)Nominal Cooling @95°F (BTU/HR)43°FWB 5°FWB-4°FWB-13°FWBLineset SizeMax Total Length (ft)Max Vertical Length (ft)Energy Star Certified
FTX09WMVJU9 + RXL09WMVJU99403 / 328 / 251 / 21510,90016,00010,9008,8106,6301/4" x 3/8"6649yes
FTX12WMVJU9 + RXL12WMVJU912413 / 321 / 258 / 21913,30018,80014,33011,5808,7201/4" x 3/8"6649yes
FTX15WMVJU9 + RXL15WMVJU915653 / 554 / 470 / 39918,40024,60018,30014,79011,1401/4" x 1/2"9866yes
FTX18WVJU9 + RXL18WMVJU918713 / 583 / 431 / 39921,60028,00021,60018,36015,1201/4" x 1/2"9866no
FTX24WVJU9 + RXL24WMVJU924699 / 572 / 445 / 40325,80032,00024,00020,40016,4201/4" x 5/8"9866no

  • All nominal capacities represent maximum capacities
  • Cooling operation range: 50°F to 115°F
  • Low ambient cooling to -4°F available with wind baffle
  • Heating operation range: -13°F to 65°F

Features

  • Cold climate Aurora with confirmed operation to -13°F and 100% capacity at 5°F
  • Anti-Corrosion Treatment on Heat Exchanger
  • Intelligent eye operation
  • 5 selectable fan speeds with Quiet and Auto
  • 3-D airflow control with horizontal and vertical flaps
  • Titanium Apatite Photocatalytic Air Purifying Filter
  • Auto restart after power failure (reinstates previous settings)
  • Powerful and ECO+ modes
  • Hydrophilic blue fin coating of indoor unit for enhanced coil cleanliness and lifespan.
  • Options for gravity drained condensate or field installed condensate pump that fits within the unit cabinet.

Electrical Information

MCA (A) / MOP (A)
TypeVoltage9 MBH12 MBH15 MBH18 MBH24 MBH
Outdoor unit208-230V / 1ph9.5 / 1513 / 1513 / 1518.7 / 2018.9 / 20

Submittal Data Sheets

9FTX09WMVJU9 + RXL09WMVJU9
12FTX12WMVJU9 + RXL12WMVJU9
15FTX15WMVJU9 + RXL15WMVJU9
18FTX18WVJU9 + RXL18WMVJU9